FIK-313-0002 Sita Sound Point – White
Sounder with 90dB output, seven sound patterns and inbuilt short circuit isolator. Supplied complete with back box and flush adaptor plate.
The Sita Soundpoint unit allows for audible indication when the system enters an alarm condition. This is an addressable unit that attaches to the loop. Implementing digital communication technology to the control panel allows for accurate data transfer at high transmission speeds.
Install the Sounder in compliance with the control panel installation manual. The installation must also meet the requirements of any local authority.
Fike recommends spacing of sounders in accordance with any local authority.
Install all wiring in compliance with the recommendations from local authorities and the specific guidelines in the control panel installation manual. Use 2-core 1.5mm² screened, fire-resistant cables with the following characteristics:
Wire the system as a screened 2-core loop that returns to the control panel. Do not use spurs in this system. Fix the surface back box to a flat vertical surface using at least two of the four mounting holes provided. You may drill the back box to allow cable access as needed. A 20mm hole is already provided at the rear. Cables terminated into the connectors, as shown below:
Terminal Description
R (RED) Loop +ve IN
Y (YELLOW) Loop +ve OUT
B (BLUE) Loop -ve IN & OUT
E Loop SCREEN IN & OUT
The Soundpoint may be flush mounted utilising the optional adaptor plate, combined with any standard single gang flush mounting back box (with a minimum internal depth of 47mm). After installing the back box securely, attach the adaptor plate using the two screws provided and terminate the loop cables directly into a flying terminal block (not supplied). Care should be taken when terminating devices to ensure all cables are correctly sleeved and connections are secure. Improper connections will prevent a system from responding properly in the event of a fire.