FIK-326-0003 Sita Sounder – Deep Base.
Sounder with 88dB output, three sound patterns and inbuilt short circuit isolator. Supplied complete with red mounting base.
The Sita Sounder unit allows for audible indication when the system enters an alarm condition. This is an addressable unit that attaches to the loop. Implementing digital communication technology to the control panel allows for accurate data transfer at high transmission speeds.
Install the Sounder in compliance with the control panel installation manual. The installation must also meet the requirements of any local authority.
Fike recommends spacing of sounders in accordance with any local authority.
Drill the cable entry region(s) in base moulding as required. Drill out the desired mounting holes through hole / slot guides as required. Affix the base moulding to a flat surface using a minimum of 2 screws. Install all wiring according to recommendations from local authorities and any special instructions specified in the control panel installation manual. The cabling should be 2-core, 1.5mm² screened, fire-resistant, and possess the following characteristics:
Wire it as a screened 2-core loop that returns to the control panel. Do not use spurs in this system. Terminate cables into the connector as shown below:
Terminal Description
L1 Loop +ve IN
0V Loop -ve IN
SCRN Screen IN
SCRN Screen OUT
0V Loop -ve OUT
L2 Loop +ve OUT
Take care when terminating devices to sleeve all cables correctly and secure connections properly. Improper connections will prevent a system from responding properly in the event of a fire.