FIK-402-0006 Twinflex Manual Call Point

Product Documents

Product Description

FIK-402-0006 Twinflex Manual Call Point with cover. A Manual call point with resettable element reset key, back box, adaptor plate for flush mount and inbuilt ‘End of Line’ set by DIL switch (includes call point cover).

The Twinflex Manual Call Point (MCP) allows for user activation of the fire alarm system. Once operated the device latches into the alarm position and requires manually resetting via a special key.

This device is compatible with the range of Twinflex Fire Alarm Control Panels and comprises a 2-wire zone-powered Manual Call Point (MCP). This device may be installed on the same zone as the Twinflex Multipoint detector/sounder and other associated Twinflex devices.

Install the MCP according to the control panel installation manual. The installation must also meet the requirements of any local authority. Fike recommends spacing of call points in accordance with any local authority.

Device Installation of FIK-402-0006

Install all wiring according to recommendations from local authorities and any special instructions in the control panel installation manual. Use 2-core, 1.5mm² screened, fire-resistant cabling (e.g., FP200 equivalent), and wire it as a screened 2-core radial circuit (with no spurs) from the control panel, terminating at the last (“End of Line”) device.

Terminate site cables into the connectors as shown overleaf. Take care when terminating devices to ensure all cables are correctly sleeved and connections are secure. Improper connections will prevent a system from responding properly in the event of a fire.