FIK-403-0006

FIK-403-0006 Sita Manual Call Point

Product Documents

Product Description

FIK-403-0006 Sita Manual Call Point. A manual call point with re-settable element, reset key, back box, adaptor plate for flush mount and inbuilt short circuit isolator (includes call point cover).

The Sita Manual Call Point allows for user activation of the fire alarm system. Once operated the device latches into the alarm position and requires manually resetting via a special key. The MCP is an addressable unit that attaches to the loop. Digital communication technology to the control panel is implemented allowing for accurate data transfer at high transmission speeds.

Install the MCP in compliance with the control panel installation manual. The installation must also meet the requirements of any local authority. Fike recommends spacing of call points in accordance with any local authority.

Device Installation of FIK-403-0006

Install all wiring according to the recommendations from local authorities and any special instructions in the control panel installation manual. Use 2-core, 1.5mm² screened, fire-resistant cabling with the following characteristics:

Max Capacitance Core to Screen: 180pF / m
Max Capacitance Core to Core: 100pF / m
Inductance (Max): 1.0mH / km
Max Resistance Two Core Screened 1.5mm²: 12.1Ω / km

Wire it as a screened 2-core loop returning to the control panel. Do not use spurs in this system.