FIK-803-0010 Sita Conventional Zone Module.
Addressable conventional zone module mounted within a standard double gang box. Provides the facility to connect 1 zone of conventional resistance monitored devices to the addressable system, up to a maximum of 20mA. EOL capacitors included. Connects to the addressable loop.
The Conventional Zone Module provides an interface between ancillary devices and the loop. Use it to connect conventional fire detection devices to the system with head removal monitoring. Power the unit directly from the loop or from a remote PSU. Implement digital communication technology to the control panel for accurate data transfer at high transmission speeds.
The CZM must be installed in compliance with the control panel installation manual. The installation must also meet the requirements of any local authority. Mount the module securely and ensure the device is accessible for future maintenance.
Install all wiring according to recommendations from local authorities and any special instructions in the control panel installation manual. Use 2-core, 1.5mm² screened, fire-resistant cabling and wire it as a screened 2-core loop returning to the control panel. Do not use spurs in this system. Take care when terminating devices to sleeve all cables correctly and secure connections properly. Improper connections will prevent a system from responding properly in the event of a fire.